Fluke 1550C FC 5 kV Digital Insulation Tester

Fluke

The tester’s accuracy is specified for one year after calibration at operating temperatures of 0°C to 35°C. For operating temperatures outside the range (-20°C to 0°C and 35°C to 50°C), add ± .25% per °C, except on the 20% bands add ± 1% per °C.

310,000.00 EGP

Fluke 1550C FC 5 kV Digital Insulation Tester

Data collection from insulation tests made easy

The Fluke 1550C performs digital insulation testing up to 5 kV, and makes data collection easy through the Fluke Connect™ wireless app. Remote operation lets you spend as little time as possible in potentially hazardous zones. Real-time trending shows a live graph on your phone, rather than a hard-to-read set of changing values. And you can create reports quickly, using pre-designed templates that you can customize with company logos. It’s the perfect tool for preventive or predictive maintenance programs designed to identify potential equipment failures before they occur. And it comes with a three-year warranty and CAT IV 600 V safety rating.

Other useful features

  • Automatic calculation of Dielectric Absorption (DAR) and Polarization Index (PI) with no additional setup
  • Guard system eliminates the effect of surface leakage current on high-resistance measurements
  • Selectable test voltages in 50 V steps from 250 V to 1000 V, and 100 V steps above 1000 V
  • CAT III 1000 V, CAT IV 600 V safety rating
  • Warning function alerts the user that line voltage is present and gives the voltage reading up to 600 V AC or DC for increased user safety
  • Measurements can be stored in up to 99 memory locations, with each location assigned a unique, user defined, label for easy recall
  • Long battery life gives the user over 750 tests between charges
  • Large digital/analog LCD for easy viewing
  • Capacitance and leakage current measurement
  • Ramp function for breakdown testing
  • Resistance measurements up to 2 TΩ
  • Timer settings up to 99 minutes for timed tests
  • 3-year warranty
SKU: Fluke 1550C FC Category: Brand:
brands

Test voltage (DC)
250 V Range < 250 kΩ,
250 kΩ to 5 GΩ
5 GΩ to 50 GΩ
> 50 GΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
500 V Range < 500 kΩ
500 kΩ to 10 GΩ
10 GΩ to 100 GΩ
> 100 GΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
1000 V Range < 1 MΩ
1 MΩ to 20 GΩ
20 GΩ to 200 GΩ
> 200 GΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
2500 V Range < 2.5 MΩ
2.5 MΩ to 50 GΩ
50 GΩ to 500 GΩ
> 500 GΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
5000 V Range < 5 MΩ
5 MΩ to 100 GΩ
100 GΩ to 1 TΩ
> 1 TΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
Bar graph range 0 to 1 TΩ (1550C) – 0 to 2 TΩ (1555)
Insulation test voltage accuracy -0%, +10% at 1 mA load current
Induced AC mains current rejection 2 mA maximum
Charging rate for capacitive load 5 seconds per μF
Discharge rate for capacitive load 1.5 s/μF
Leakage current measurement Range 1 nA to 2 mA
Accuracy ± (5% + 2 nA)
Capacitance measurement Range 0.01 μF to 15.00 μF
Accuracy ± (15% rdg + 0.03 μF)
Timer Range 0 to 99 minutes
Resolution setting 1 minute
Resolution indication 1 second
Live circuit warning Warning range 30 V to 660 V AC/DC, 50/60 Hz
Voltage accuracy ± (15% + 2 V)
Software specifications FlukeView Forms™ basic software requires a PC running Windows XP, Windows Vista , Windows 7 or Windows 8.
Test voltage (DC)
250 V Range < 250 kΩ, 250 kΩ to 5 GΩ 5 GΩ to 50 GΩ > 50 GΩ
Accuracy (± reading) Unspecified 5% 20% Unspecified
500 V Range < 500 kΩ 500 kΩ to 10 GΩ 10 GΩ to 100 GΩ > 100 GΩ
Accuracy (± reading) Unspecified 5% 20% Unspecified
1000 V Range < 1 MΩ 1 MΩ to 20 GΩ 20 GΩ to 200 GΩ > 200 GΩ
Accuracy (± reading) Unspecified 5% 20% Unspecified
2500 V Range < 2.5 MΩ 2.5 MΩ to 50 GΩ 50 GΩ to 500 GΩ > 500 GΩ
Accuracy (± reading) Unspecified 5% 20% Unspecified
5000 V Range < 5 MΩ 5 MΩ to 100 GΩ 100 GΩ to 1 TΩ > 1 TΩ
Accuracy (± reading) Unspecified 5% 20% Unspecified
Bar graph range 0 to 1 TΩ (1550C) - 0 to 2 TΩ (1555)
Insulation test voltage accuracy -0%, +10% at 1 mA load current
Induced AC mains current rejection 2 mA maximum
Charging rate for capacitive load 5 seconds per μF
Discharge rate for capacitive load 1.5 s/μF
Leakage current measurement Range 1 nA to 2 mA
Accuracy ± (5% + 2 nA)
Capacitance measurement Range 0.01 μF to 15.00 μF
Accuracy ± (15% rdg + 0.03 μF)
Timer Range 0 to 99 minutes
Resolution setting 1 minute
Resolution indication 1 second
Live circuit warning Warning range 30 V to 660 V AC/DC, 50/60 Hz
Voltage accuracy ± (15% + 2 V)
Software specifications FlukeView Forms™ basic software requires a PC running Windows XP, Windows Vista , Windows 7 or Windows 8.

Datasheet

Datasheet

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “Fluke 1550C FC 5 kV Digital Insulation Tester”

There are no reviews yet.

SHOPPING CART

close