Compare

This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 64 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to 15th Harmonic. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 415 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 35 to 690 VAC at 47 to 63 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 47 to 63 Hz. Communication is pulse output only. The meter also has 33 configurable alarms. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 2.83 inches (72 millimetres), height 3.78 inches (96 millimetres) and product weight 13.4 onces (380 g).

Main
Range PowerLogic
Product name PowerLogic PM5000
Device short name PM5100
Product or component type Power meter
Complementary
Power quality analysis Up to the 15th harmonic
Device application Power monitoring
Type of measurement Current
Voltage
Frequency
Power factor
Energy
Active and reactive power
supply voltage 90…450 V AC 45…65 Hz
100…300 V DC
Network frequency 60 Hz
50 Hz
[In] rated current 5 A
1 A
type of network 3P + N
1P + N
3P
Maximum power consumption in VA 11 VA at 415 V
Ride-through time 80 ms 120 V AC typical
100 ms 230 V AC typical
100 ms 415 V AC typical
50 ms 125 V DC typical
Display type Monochrome graphic LCD
Display resolution 128 x 128 pixels
Sampling rate 64 samples/cycle
Measurement current 50…8500 mA
Analogue input type Voltage (impedance 5 MOhm)
Current (impedance <= 0.3 mOhm)
Measurement voltage 35…760 V AC 45…65 Hz between phases
20…400 V AC 45…65 Hz between phase and neutral
Frequency measurement range 45…65 Hz
Number of inputs 0
Measurement accuracy Active energy +/- 0.5 %
Reactive energy +/- 2 %
Active power +/- 0.5 %
Apparent power +/- 0.5 %
Frequency +/- 0.05 %
Power factor +/- 0.5
Current +/- 0.5 %
Voltage +/- 0.5 %
Apparent energy +/- 0.5 %
Reactive power +/- 2 %
Accuracy class Class 0.5S active energy conforming to IEC 62053-22
Number of outputs 1 pulse (energy)
Communication port protocol
Communication port support
data recording Min/max of instantaneous values
Time stamping
Connections – terminals Voltage circuit: screw terminal block4
Control circuit: screw terminal block2
Current transformer: screw terminal block6
Input/output circuit: screw terminal block6
RS485 link: screw terminal block4
Mounting mode Flush-mounted
Mounting support Framework
Standards EN 50470-1
IEC 62053-22:2020
UL 61010-1
IEC 62053-24
IEC 61557-12:2015
EN 50470-3
IEC 60529
IEC 62053-23:2020
IEC 62052-11:2020
IEC 62052-31:2015
Product certifications CE conforming to IEC 61010-1
CULus conforming to UL 61010-1
Width 96 mm
Depth 72 mm
height 96 mm
Net weight 380 g
Environment
Electromagnetic compatibility Limits for harmonic current emissions class A conforming to IEC 61000-3-2
Electrostatic discharge level 4 conforming to IEC 61000-4-2
Conducted RF disturbances level 3 conforming to IEC 61000-4-6
Magnetic field at power frequency level 4 conforming to IEC 61000-4-8
Conducted and radiated emissions class B conforming to EN 55022
Immunity to conducted disturbances – test level: 150 kHz…80 MHz conforming to IEC 61000-4-6
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
Surge immunity test conforming to IEC 61000-4-5
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
IP degree of protection IP54 display: conforming to IEC 60529
IP30 rear: conforming to IEC 60529
Relative humidity 5…95 % at 50 °C non-condensing
Pollution degree 2
Ambient air temperature for operation -25…70 °C meter
-20…70 °C display
-25…-20 °C (with reduced performance) display
Ambient air temperature for storage -40…85 °C
Operating altitude 2000 m CAT III
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 11.0 cm
Package 1 Width 12.6 cm
Package 1 Length 12.6 cm
Package 1 Weight 550.0 g
Unit Type of Package 2 S03
Number of Units in Package 2 12
Package 2 Height 30.0 cm
Package 2 Width 30.0 cm
Package 2 Length 40.0 cm
Package 2 Weight 6.54 kg
Unit Type of Package 3 P06
Number of Units in Package 3 96
Package 3 Height 50.0 cm
Package 3 Width 80.0 cm
Package 3 Length 60.0 cm
Package 3 Weight 61.44 kg

Main Document