Schneider A9F75116 Description

This Acti9 iC60N is a low voltage miniature circuit breaker (MCB).
It is a 1P circuit breaker with 1 protected pole, 16A rated current and D tripping curve.
The rated short circuit breaking capacity goes up to 10kA at 220VAC to 240VAC conforming to EN/IEC 60947-2 standard and 6000A at 230VAC conforming to EN/IEC 60898-1 standard.
It complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2.
This miniature circuit breaker protects circuits against short circuit and overload current.
Its unique VisiTrip indicator reduces intervention time by showing the faulty circuit.
Its VisiSafe green strip guarantees the physical opening of the contacts to allow downstream maintenance. Its fast closing mechanism independent of manual operation improves its service life.
It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ui rated insulation voltage is 500VAC.
Its limitation class 3 (according to EN/IEC60898-1) improves downstream circuit protection cost.
The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm.
Pollution degree is 3. Overvoltage category is IV.
The product colour is white (RAL9003).
The dimensions are (W) 18mm x (H) 85mm x (D) 78.5mm.
The weight is 0.215kg. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure.
The operating temperature is -35°C to 70°C. The storage temperature is -40°C to 85°C.

The Schneider A9F75116 is a miniature circuit breaker (MCB) from the Schneider Electric Acti 9 series. Here’s a detailed description of its features and specifications:

  1. Type: 1-pole, 1-module device.
  2. Current Rating: Rated for 16 amps.
  3. Voltage: Suitable for voltages up to 240V AC.
  4. Breaking Capacity: Provides a breaking capacity of 10 kA according to IEC/EN 60898-1 standard.
  5. Trip Curve: C-curve characteristic, meaning it trips in response to overload currents between 5 to 10 times the rated current.

Applications:

  • Ideal for protecting electrical circuits in residential, commercial, and industrial installations.
  • Commonly used in distribution boards and consumer units where single-pole protection is required.

Features:

  • Compact and modular design for efficient use of space in electrical panels.
  • DIN rail mountable for easy and quick installation.
  • High reliability and durability, ensuring long-term performance.
  • Provides effective protection against overloads and short circuits, contributing to the safety and reliability of electrical systems.

The Schneider A9F75116 MCB is engineered to offer robust and efficient circuit protection, ensuring the safety and integrity of electrical installations acrossa variety of applications.

SKU: A9F75116 Categories: ,
brands

Main
Device applicationDistribution
RangeActi9
Product nameActi9 iC60
product or component typeMiniature circuit-breaker
Device short nameIC60N
poles description1P
Number of protected poles1
[In] rated current16 A
Network typeDC
AC
Trip unit technologyThermal-magnetic
Curve codeD
Breaking capacity6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
10 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
15 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2
10 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
Utilisation categoryCategory A conforming to EN 60947-2
Category A conforming to IEC 60947-2
Suitability for isolationYes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2
StandardsIEC 60898-1
EN 60898-1
IEC 60947-2
EN 60947-2
Complementary
Network frequency50/60 Hz
Magnetic tripping limit12 x In +/- 20 %
[Ics] rated service breaking capacity27 kA 75 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 75 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
27 kA 75 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 75 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
15 kA 75 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15 kA 75 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
6000 A 100 % conforming to EN 60898-1 – 230 V AC 50/60 Hz
6000 A 100 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
10 kA 100 % conforming to EN 60947-2 – 72 V DC
10 kA 100 % conforming to IEC 60947-2 – 72 V DC
15 kA 100 % conforming to EN 60947-2 – 12…60 V DC
15 kA 100 % conforming to IEC 60947-2 – 12…60 V DC
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2
Contact position indicatorYes
Control typeToggle
local signallingTrip indicator
mounting modeFixed
mounting supportDIN rail
Comb busbar and distribution block compatibilityTop or bottom: YES
9 mm pitches2
Height85 mm
Width18 mm
Depth78.5 mm
net weight0.215 kg
ColourWhite
Mechanical durability20000 cycles
Electrical durability10000 cycles
Connections – terminalsSingle terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible
Wire stripping length14 mm for top or bottom connection
Tightening torque2 N.m top or bottom
Earth-leakage protectionWithout
Environment
IP degree of protectionIP20 conforming to IEC 60529
IP20 conforming to EN 60529
Pollution degree3 conforming to EN 60947-2
3 conforming to IEC 60947-2
Overvoltage categoryIV
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Operating altitude0…2000 m
Ambient air temperature for operation-35…70 °C
Ambient air temperature for storage-40…85 °C
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height1.8 cm
Package 1 Width7.5 cm
Package 1 Length9.5 cm
Package 1 Weight109.0 g
Unit Type of Package 2BB1
Number of Units in Package 212
Package 2 Height8.0 cm
Package 2 Width9.5 cm
Package 2 Length22.5 cm
Package 2 Weight1.372 kg
Unit Type of Package 3S03
Number of Units in Package 3132
Package 3 Height30.0 cm
Package 3 Width30.0 cm
Package 3 Length40.0 cm
Package 3 Weight15.618 kg
Contractual warranty
Warranty18 months

Main Document

Data Sheet : Download

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “Schneider A9F75116 | Miniature circuit breaker (MCB), Acti9 iC60N, 1P, 16A, D curve, 6000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)”

There are no reviews yet.

SHOPPING CART

close
error: Content is protected !!
Let's Chat