Schneider A9F77332 | Miniature circuit-breaker, Acti9 iC60N, 3P, 32 A, C curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2)

Schneider Electric
Availability:

Out of stock


Schneider A9F77332 | Miniature circuit-breaker, Acti9 iC60N, 3P, 32 A, C curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2)

1,526.00 EGP 2,329.70 EGP

Out of stock

Schneider A9F77332 | Miniature circuit-breaker, Acti9 iC60N, 3P, 32 A, C curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2)

Technical Specifications

  • Model: Schneider A9F77332

  • Series: Acti9 iC60N

  • Type: Miniature Circuit Breaker (MCB)

  • Poles: 3P (3 poles)

  • Rated Current: 32A

  • Curve Type: C curve (for general-purpose applications with moderate inrush currents)

  • Breaking Capacity:

    • 6000 A as per IEC 60898-1 (for residential and commercial protection)

    • 10 kA as per IEC 60947-2 (for industrial applications)

  • Rated Voltage: 415V (commonly used for 3-phase electrical systems)

  • Mounting Type: DIN rail (standard for electrical panel installations)

  • Certifications: Complies with IEC 60898-1 and IEC 60947-2

  • Weight: Approximately 0.56 kg

Key Features

  1. High Breaking Capacity: The Schneider A9F77332 MCB offers a high breaking capacity of 6000 A (IEC 60898-1) and 10 kA (IEC 60947-2), ensuring it can handle large fault currents and provide dependable protection for circuits and equipment.

  2. 3-Pole Configuration: This circuit breaker features a 3-pole (3P) design, making it ideal for protecting 3-phase circuits commonly used in commercial and industrial applications. It ensures the protection of all three phases of a circuit simultaneously.

  3. C Curve Protection: The C curve characteristic is specifically designed for general-purpose applications that involve moderate inrush currents. It provides a balanced response to both overloads and short circuits, making it suitable for inductive loads like motors and transformers.

  4. DIN Rail Mounting: The A9F77332 is designed for DIN rail mounting, ensuring easy installation in distribution boards and electrical panels. The standard mounting system makes it easy to integrate into a wide variety of electrical setups.

  5. Durability and Safety: This MCB offers overload protection and short-circuit protection, safeguarding electrical circuits and connected devices from damage caused by excessive current or faults. It is built to be durable and reliable, providing long-lasting performance in demanding environments.

  6. Compact Design: Despite its high performance, the A9F77332 is compact, allowing for space-efficient installations in electrical panels. Its small size ensures that multiple circuit breakers can be installed in a limited space while still providing optimal protection.

Applications

  1. Industrial Applications: The Schneider A9F77332 is ideal for use in industrial settings where 3-phase power systems are common. It protects motors, industrial machines, and transformers from damage due to overloads and short circuits, ensuring smooth and safe operations.

  2. Commercial Electrical Systems: In commercial environments, this MCB is used to protect power distribution circuits, HVAC systems, lighting systems, and other essential equipment. It provides reliable protection against electrical faults, minimizing downtime and the risk of equipment damage.

  3. Residential Installations: The A9F77332 can be used in residential buildings with 3-phase electrical systems. It ensures the safety of high-power appliances and electrical circuits, including air conditioners, large refrigerators, and other heavy-duty devices.

  4. Renewable Energy Systems: This circuit breaker is also suitable for protecting circuits in solar energy systems and other renewable energy setups that use 3-phase power. It helps protect the electrical components from faults that could occur during the operation of such systems.

  5. Power Distribution Panels: The A9F77332 is commonly used in power distribution panels to protect circuits that require moderate to high protection against overloads and short circuits. It ensures that the electrical system remains operational and secure in case of power fluctuations or faults.

Main
Device application Distribution
Range Acti9
Product name Acti9 iC60
product or component type Miniature circuit-breaker
Device short name IC60N
Poles description 3P
Number of protected poles 3
[In] rated current 32 A
Network type AC
DC
Trip unit technology Thermal-magnetic
Curve code C
Breaking capacity 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at <= 180 V DC conforming to EN/IEC 60947-2
Utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2
Suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2
Standards IEC 60898-1
EN 60898-1
EN 60947-2
IEC 60947-2
Quality labels NF
Complementary
Network frequency 50/60 Hz
Magnetic tripping limit 8 x In +/- 20 %
[Ics] rated service breaking capacity 15 kA 75 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 75 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
27 kA 75 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
27 kA 75 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
6000 A 100 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
6000 A 100 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
10 kA 100 % conforming to IEC 60947-2 – 125…180 V DC
10 kA 100 % conforming to EN 60947-2 – 125…180 V DC
Limitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1
[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2
Contact position indicator Yes
Control type Toggle
Local signalling Trip indicator
Mounting mode Fixed
Mounting support DIN rail
Comb busbar and distribution block compatibility Top or bottom: YES
9 mm pitches 6
Height 85 mm
Width 54 mm
Depth 78.5 mm
net weight 0.375 kg
Colour White
Mechanical durability 20000 cycles
Electrical durability 10000 cycles
Connections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible
Wire stripping length 14 mm for top or bottom connection
Tightening torque 3.5 N.m top or bottom
earth-leakage protection Separate block
Environment
IP degree of protection IP20 conforming to IEC 60529
IP20 conforming to EN 60529
Pollution degree 3 conforming to EN 60947-2
3 conforming to IEC 60947-2
Overvoltage category IV
Tropicalisation 2 conforming to IEC 60068-1
Relative humidity 95 % at 55 °C
Operating altitude 0…2000 m
Ambient air temperature for operation -35…70 °C
ambient air temperature for storage -40…85 °C
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 7.3 cm
Package 1 Width 5.4 cm
Package 1 Length 8.5 cm
Package 1 Weight 360 g
Unit Type of Package 2 BB1
Number of Units in Package 2 4
Package 2 Height 8.1 cm
Package 2 Width 9.8 cm
Package 2 Length 22.4 cm
Package 2 Weight 1.505 kg
Unit Type of Package 3 S03
Number of Units in Package 3 44
Package 3 Height 30 cm
Package 3 Width 30 cm
Package 3 Length 40 cm
Package 3 Weight 17.043 kg
Contractual warranty
Warranty 18 months

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “Schneider A9F77332 | Miniature circuit-breaker, Acti9 iC60N, 3P, 32 A, C curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2)”

There are no reviews yet.

SHOPPING CART

close
Let's Chat