55 kW at 230 V connection in the motor supply line for severe applications 75 kW at 230 V connection in the motor supply line for standard applications 110 kW at 230 V connection to the motor delta terminals for severe applications 110 kW at 400 V connection in the motor supply line for severe applications 132 kW at 230 V connection to the motor delta terminals for standard applications 132 kW at 400 V connection in the motor supply line for standard applications 160 kW at 400 V connection to the motor delta terminals for severe applications 220 kW at 400 V connection to the motor delta terminals for standard applications
Complementary
device connection
To the motor delta terminals In the motor supply line
Protection type
Phase failure: line Thermal protection: motor Thermal protection: starter
Standards
EN/IEC 60947-4-2
product certifications
C-Tick CCC UL NOM 117 CSA DNV SEPRO GOST TCF
Marking
CE
Discrete input number
5
Discrete input type
PTC, 750 Ohm at 25 °C (Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
Discrete input logic
Positive logic Stop, Run, LI3, LI4 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA
Minimum switching current
10 mA at 6 V DC for relay outputs
Discrete output number
2
Discrete output type
(LO1) logic output 0 V common configurable (LO2) logic output 0 V common configurable (R1) relay outputs fault relay NO (R2) relay outputs end of starting relay NO (R3) relay outputs motor powered NO
Analogue output type
Current output AO: 0-20 mA or 4-20 mA, impedance <500 Ohm
communication port protocol
Modbus
Connector type
1 RJ45
Communication data link
Serial
Physical interface
RS485 multidrop
Transmission rate
4800, 9600 or 19200 bps
Function available
External bypass (optional)
Operating position
Vertical +/- 10 degree
height
380 mm
Width
320 mm
Depth
265 mm
Net weight
18.2 kg
Environment
Electromagnetic compatibility
Conducted and radiated emissions level A conforming to IEC 60947-4-2 Damped oscillating waves level 3 conforming to IEC 61000-4-12 Electrostatic discharge level 3 conforming to IEC 61000-4-2 Immunity to electrical transients level 4 conforming to IEC 61000-4-4 Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3 Voltage/current impulse level 3 conforming to IEC 61000-4-5
Relative humidity
0…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
Ambient air temperature for operation
40…60 °C (with current derating of 2 % per °C) -10…40 °C (without derating)
Ambient air temperature for storage
-25…70 °C
Operating altitude
<= 1000 m without derating > 1000…2000 m with current derating of 2.2 % per additional 100 m
There are no reviews yet.