-34%
,

Schneider C25B3TM250 | Circuit breaker ComPacT NSX250B, 25kA at 415VAC, TMD trip unit 250A, 3 poles 3d

Schneider Electric
Availability:

Out of stock


Schneider C25B3TM250 | Circuit breaker ComPacT NSX250B, 25kA at 415VAC, TMD trip unit 250A, 3 poles 3d

19,494.68 EGP 29,537.40 EGP

Out of stock

Schneider C25B3TM250: Product Overview and Applications

Introduction

The Schneider C25B3TM250 is a high-capacity molded case circuit breaker (MCCB) with a rated current of 250A, designed for demanding electrical systems that require superior circuit protection. This MCCB is built to safeguard against overloads, short circuits, and faults in large-scale and high-power applications. Equipped with both thermal and magnetic trip mechanisms, the C25B3TM250 is suitable for industrial, commercial, and heavy-duty electrical infrastructures where reliable performance and safety are paramount.

Key Features of Schneider C25B3TM250

  • High Current Rating (250A): Designed to handle large power loads, making it ideal for industrial and commercial systems with high electrical demands.
  • Thermal-Magnetic Trip Unit: Offers dual protection, with thermal sensing for overloads and magnetic sensing for instantaneous response to short circuits.
  • High Breaking Capacity: Capable of safely interrupting high fault currents, ensuring system integrity under heavy electrical loads.
  • Durable and Compact Construction: Engineered for longevity, with a design that fits well into standard panels without compromising on performance.
  • Adjustable Trip Settings: Provides customizable protection settings to cater to specific application needs, enhancing both safety and operational flexibility.

Applications of Schneider C25B3TM250

  1. Industrial Machinery Protection: Safeguards heavy-duty equipment such as motors, compressors, and conveyor systems in manufacturing environments.
  2. Commercial Power Distribution: Ideal for high-demand commercial facilities, providing reliable circuit protection for lighting, HVAC, and other power-intensive systems.
  3. Data Centers and IT Infrastructure: Ensures dependable power distribution and circuit protection in data centers, where uninterrupted power is critical.
  4. Utility and Substation Networks: Suitable for power distribution in utility networks, substations, and critical infrastructure that require fault tolerance and high reliability.
  5. Renewable Energy Systems: Provides dependable circuit protection in large-scale renewable energy applications, such as solar power installations and energy storage systems.

Benefits of Using Schneider C25B3TM250

  • Reliable Circuit Protection for Heavy Loads: Delivers robust protection for large-capacity electrical systems, reducing the risk of equipment damage and downtime.
  • Versatile for Multiple Applications: Adaptable to a variety of settings, with adjustable trip settings that allow it to cater to both industrial and commercial requirements.
  • Compact and Efficient Design: Built for efficient panel integration, saving space while delivering powerful circuit protection.
  • Minimal Maintenance Requirements: Designed for long-lasting performance with minimal maintenance, making it cost-effective over time.

Conclusion

The Schneider C25B3TM250 is a robust, high-capacity MCCB, perfect for safeguarding circuits in demanding industrial and commercial settings. With its 250A rating, high breaking capacity, and thermal-magnetic trip unit, this MCCB is engineered to handle heavy electrical loads and protect critical systems. Its versatility, durability, and adjustable settings make it an ideal choice for applications ranging from industrial machinery to utility networks, where safe and reliable circuit protection is essential.

SKU: C25B3TM250 Categories: , Brand:
Main
Range ComPacT new generation
Product name ComPacT NSX new generation
Device short name NSX250B
product or component type Circuit breaker
Device application Distribution
poles description 3P
Protected poles description 3D
[In] rated current 250 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN/IEC 60947-2
Utilisation category Category A
[Icu] rated ultimate short-circuit breaking capacity 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Performance level B 25 kA 415 V AC
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit protection functions LI
Control type Toggle
Circuit breaker mounting mode Fixed
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
[Ics] rated service short-circuit breaking capacity 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 20000 cycles
Electrical durability 20000 cycles at 440 V In/2
10000 cycles at 440 V In
10000 cycles at 690 V In/2
5000 cycles at 690 V In
Power dissipation per pole 18.75 W
mounting support Backplate
Mounting position Horizontal and vertical
Flat on the back
Upside connection Front
downside connection Front
Connection pitch 35 mm
Protection type L : for overload protection (thermal)
I : for short-circuit protection (magnetic)
Trip unit rating 250 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection) Adjustable
[Ir] long-time protection pick-up adjustment range 0.7…1 x In
Long-time protection delay adjustment type tr Fixed
[tr] long-time protection delay adjustment range 120…400 s at 1.5 x In
15 s at 6 x Ir
Instantaneous protection pick-up adjustment type Ii Adjustable
[Ii] instantaneous protection pick-up adjustment range 5…10 x In
Earth-leakage protection Without
Number of slots for electrical auxiliaries 5 slot(s)
Width (W) 105 mm
Height (H) 161 mm
Depth (D) 86 mm
net weight 2.4 kg
Environment
Standards EN/IEC 60947
Product certifications CCC
EAC
Marine
Overvoltage category Class II
Electrical shock protection class Class II
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -25…70 °C
ambient air temperature for storage -50…85 °C
Relative humidity 0…95 %
Operating altitude 0…2000 m without derating
2000 m…5000 m with derating
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 14.000 cm
Package 1 Width 11.000 cm
Package 1 Length 19.000 cm
Package 1 Weight 1.900 kg
Unit Type of Package 2 S03
Number of Units in Package 2 7
Package 2 Height 30.000 cm
Package 2 Width 30.000 cm
Package 2 Length 40.000 cm
Package 2 Weight 14.394 kg

Main
Range ComPacT new generation
Product name ComPacT NSX new generation
Device short name NSX250B
product or component type Circuit breaker
Device application Distribution
poles description 3P
Protected poles description 3D
[In] rated current 250 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN/IEC 60947-2
Utilisation category Category A
[Icu] rated ultimate short-circuit breaking capacity 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Performance level B 25 kA 415 V AC
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit protection functions LI
Control type Toggle
Circuit breaker mounting mode Fixed
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
[Ics] rated service short-circuit breaking capacity 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 20000 cycles
Electrical durability 20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Power dissipation per pole 18.75 W
mounting support Backplate
Mounting position Horizontal and vertical Flat on the back
Upside connection Front
downside connection Front
Connection pitch 35 mm
Protection type L : for overload protection (thermal) I : for short-circuit protection (magnetic)
Trip unit rating 250 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection) Adjustable
[Ir] long-time protection pick-up adjustment range 0.7...1 x In
Long-time protection delay adjustment type tr Fixed
[tr] long-time protection delay adjustment range 120…400 s at 1.5 x In 15 s at 6 x Ir
Instantaneous protection pick-up adjustment type Ii Adjustable
[Ii] instantaneous protection pick-up adjustment range 5...10 x In
Earth-leakage protection Without
Number of slots for electrical auxiliaries 5 slot(s)
Width (W) 105 mm
Height (H) 161 mm
Depth (D) 86 mm
net weight 2.4 kg
Environment
Standards EN/IEC 60947
Product certifications CCC EAC Marine
Overvoltage category Class II
Electrical shock protection class Class II
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -25…70 °C
ambient air temperature for storage -50…85 °C
Relative humidity 0…95 %
Operating altitude 0...2000 m without derating 2000 m...5000 m with derating
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 14.000 cm
Package 1 Width 11.000 cm
Package 1 Length 19.000 cm
Package 1 Weight 1.900 kg
Unit Type of Package 2 S03
Number of Units in Package 2 7
Package 2 Height 30.000 cm
Package 2 Width 30.000 cm
Package 2 Length 40.000 cm
Package 2 Weight 14.394 kg

Main Document

Data Sheet : Download

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “Schneider C25B3TM250 | Circuit breaker ComPacT NSX250B, 25kA at 415VAC, TMD trip unit 250A, 3 poles 3d”

There are no reviews yet.

SHOPPING CART

close

congratulations

شكرا لك علي التسجيل ويشرفنا تواجدك معانا لانك شريك لدينا مهم

فندق انتركونتيننتال سيتى ستارز قاعة السرايا بتاريخ 22-09-2024