-46%
,

Schneider GV2ME14 | Motor circuit breaker, TeSys GV2, 3P, 6-10 A, thermal magnetic, screw clamp terminals

Availability:

Out of stock


2,950 EGP 5,463 EGP

Out of stock

Compare

Schneider GV2ME14 | Motor circuit breaker, TeSys GV2, 3P, 6-10 A, thermal magnetic, screw clamp terminals

The Schneider Electric GV2ME14 is a motor circuit breaker from the GV2 series, designed to provide reliable protection for motors and electrical circuits. Here’s a detailed description of the GV2ME14:

Schneider Electric GV2ME14 Motor Circuit Breaker

General Description:

  • Series: GV2
  • Product Type: Motor Circuit Breaker
  • Function: The GV2ME14 is designed to protect motors against short circuits, overloads, and phase failures, ensuring reliable operation and safety.

Technical Specifications:

  • Rated Current (In): Adjustable from 9 A to 14 A
  • Poles: 3 poles
  • Breaking Capacity: High breaking capacity suitable for industrial applications.
  • Rated Operational Voltage (Ue): Up to 690 V AC
  • Trip Unit: Thermal-magnetic trip unit provides overload and short-circuit protection.

Design and Construction:

  • Size: Compact design for easy integration into motor control panels and distribution boards.
  • Material: Constructed from high-quality materials to ensure durability and reliability under demanding conditions.
  • Mounting: Suitable for DIN rail mounting, allowing for easy installation and maintenance.

Features:

  • Thermal-Magnetic Trip: Provides dual protection with a thermal element for overload conditions and a magnetic element for short-circuit conditions.
  • Adjustable Settings: Adjustable trip settings allow customization based on motor requirements, ensuring optimal protection.
  • Manual Control: Equipped with a manual ON/OFF control and a reset button for ease of use.
  • Indicator: Clear trip indication for easy identification of the breaker status.

Applications:

  • Motor Protection: Ideal for protecting small to medium-sized motors in various industrial applications, including manufacturing, HVAC systems, and automation processes.
  • Electrical Distribution: Suitable for use in motor control centers and electrical distribution panels.

Certifications and Standards:

  • Compliance: Conforms to international standards such as IEC 60947-2 and IEC 60947-4-1, ensuring adherence to safety and performance requirements.
  • Certifications: CE, UL, CSA, and other regional certifications affirm compliance with established quality and safety standards.

Advantages:

  • Reliability: High breaking capacity and robust trip mechanisms ensure dependable protection for motor circuits, minimizing downtime and enhancing system reliability.
  • Versatility: Adjustable trip settings and compact design make it suitable for a wide range of industrial applications.
  • Ease of Installation: DIN rail mounting and compact design simplify installation and maintenance processes.
  • Durability: Constructed with durable materials to withstand harsh industrial environments, ensuring long-term performance and reliability.

Summary

The Schneider Electric GV2ME14 motor circuit breaker is a reliable and versatile solution for protecting motors from overloads, short circuits, and phase failures in various industrial settings. With its thermal-magnetic trip unit, adjustable settings, and durable construction, it provides robust protection while offering ease of installation and maintenance. This makes the GV2ME14 an ideal choice for safeguarding motor circuits in demanding applications.

brands

Schneider Electric

Main
RangeTeSys Deca
Product nameTeSys GV2
TeSys Deca
product or component typeMotor circuit breaker
Device short nameGV2ME
Device applicationMotor protection
Trip unit technologyThermal-magnetic
Complementary
poles description3P
Network typeAC
Utilisation categoryCategory A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
AC-3e conforming to IEC 60947-4-1
Network frequency50/60 Hz conforming to IEC 60947-4-1
Fixing mode35 mm symmetrical DIN rail: clipped
Panel: screwed (with adaptor plate)
Motor power kW3 kW at 400/415 V AC 50/60 Hz
4 kW at 400/415 V AC 50/60 Hz
4 kW at 500 V AC 50/60 Hz
5.5 kW at 500 V AC 50/60 Hz
5.5 kW at 690 V AC 50/60 Hz
7.5 kW at 690 V AC 50/60 Hz
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Control typePush-button
[In] rated current10 A
Thermal protection adjustment range6…10 A conforming to IEC 60947-4-1
Magnetic tripping current138 A
[Ith] conventional free air thermal current10 A conforming to IEC 60947-4-1
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2
Phase failure sensitivityYes conforming to IEC 60947-4-1
Suitability for isolationYes conforming to IEC 60947-1 § 7-1-6
Power dissipation per pole2.5 W
Mechanical durability100000 cycles
Electrical durability100000 cycles for AC-3 at 415 V In
100000 cycles for AC-3e at 415 V In
Rated dutyContinuous conforming to IEC 60947-4-1
Tightening torque1.7 N.m – on screw clamp terminal
Width45 mm
Height89 mm
Depth78.5 mm
net weight0.26 kg
ColourDark grey
Environment
StandardsEN/IEC 60947-2
EN/IEC 60947-4-1
Product certificationsCCC
UL
CSA
EAC
ATEX
LROS (Lloyds register of shipping)
BV
RINA
DNV-GL
UKCA
IK degree of protectionIK04
IP degree of protectionIP20 conforming to IEC 60529
Climatic withstandConforming to IACS E10
Ambient air temperature for storage-40…80 °C
Fire resistance960 °C conforming to IEC 60695-2-11
Ambient air temperature for operation-20…60 °C
Mechanical robustnessShocks: 30 Gn for 11 ms
Vibrations: 5 Gn, 5…150 Hz
Operating altitude2000 m
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height4.500 cm
Package 1 Width8.500 cm
Package 1 Length9.000 cm
Package 1 Weight272.000 g
Unit Type of Package 2S02
Number of Units in Package 224
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight6.773 kg
Unit Type of Package 3P06
Number of Units in Package 3384
Package 3 Height75.000 cm
Package 3 Width80.000 cm
Package 3 Length60.000 cm
Package 3 Weight116.368 kg
Contractual warranty
Warranty18 months

Main Document

Data Sheet : Download

Based on 0 reviews

0.0 overall