-46%
,

Schneider GVAD1010 | TeSys GV2 & GV3 – auxiliary contact – 1 NO + 1 NO (fault)

Schneider Electric
Availability:

In stock


983 EGP 1,821 EGP

In stock

Compare

Schneider GVAD1010 | TeSys GV2 & GV3 – auxiliary contact – 1 NO + 1 NO (fault)

Schneider GVAD1010 | TeSys GV2 & GV3 – Auxiliary Contact – 1 NO + 1 NO (Fault)

The Schneider GVAD1010 is a reliable auxiliary contact block designed specifically for use with TeSys GV2 and GV3 motor circuit breakers. Featuring two Normally Open (1 NO + 1 NO) contacts, this unit is ideal for applications that require additional signaling or control functionalities—especially for fault indication and remote monitoring.

General Information:

  • Brand: Schneider Electric

  • Series: TeSys GV2 & GV3

  • Model Number: GVAD1010

  • Product Type: Auxiliary Contact Block

  • Contact Configuration: 1 NO (indication) + 1 NO (fault)

Key Features:

  • Double Normally Open Contacts: Offers greater flexibility in signaling, with one contact for general indication and another for fault status

  • Designed for TeSys GV2/GV3: Ensures perfect mechanical and electrical compatibility with Schneider motor circuit breakers

  • Snap-On Mounting: Quick and secure installation on the side of GV2 or GV3 devices

  • Compact and Durable: Space-saving design with robust performance in industrial settings

  • Visual Markings: Clear identification of terminals and contacts for easy wiring

Technical Specifications:

  • Contact Type: 1 NO + 1 NO

  • Rated Operational Current (Ie): Up to 10 A

  • Rated Insulation Voltage (Ui): 690 V AC

  • Conformity Standards: IEC 60947-5-1

  • Mounting Location: Side-mounted

  • Protection Rating: IP20 (finger-safe)

  • Operating Temperature: -5°C to +60°C

Applications:

  • Fault signaling in motor protection systems

  • Status feedback to control panels or PLCs

  • Auxiliary control functions in automated machinery

  • Enhancing TeSys GV motor starter functionalities

  • Alarm triggering systems for maintenance alerts

Benefits:

  • Improves operational visibility by providing dual signaling points

  • Simple integration into existing Schneider motor control solutions

  • Saves space while increasing functionality

  • Reduces installation time with tool-free snap-on design

  • Ensures safe, reliable operation in industrial environments

Main
RangeTeSys
TeSys Deca
Device short nameGVAD
Product or component typeeAuxiliary contact block
Product compatibilityGV2L
GV2P
GV2RT
GV3L
GV2LE
GV3P
GV2ME
Mounting locationLeft side
Auxiliary contacts operationFault signal 1 NO
Pole contact composition2 NO
Complementary
[Ui] rated insulation voltage690 V conforming to IEC 60947-1
300 V conforming to UL 508
300 V conforming to CSA C22.2 No 14
[Ue] rated operational voltage48…690 V AC
24…240 V DC
[Ith] conventional free air thermal current6 A
2.5 A for fault signalling
Mechanical durability100000 cycles
Minimum switching current5 mA
Minimum switching voltage17 V
Protection typeGB2CB… circuit breaker
GG fuse 10 A
Rated operational power in VA300 VA at 48 V AC-15 – electrical durability: 100000 cycles
414 VA at 690 V AC-15 – electrical durability: 100000 cycles
500 VA at 110…127 V AC-15 – electrical durability: 100000 cycles
500 VA at 500 V AC-15 – electrical durability: 100000 cycles
650 VA at 440 V AC-15 – electrical durability: 100000 cycles
720 VA at 230…240 V AC-15 – electrical durability: 100000 cycles
850 VA at 380…415 V AC-15 – electrical durability: 100000 cycles
36 VA at 24 V AC-14 – electrical durability: 1000 cycles
48 VA at 48 V AC-14 – electrical durability: 1000 cycles
72 VA at 110…127 V AC-14 – electrical durability: 1000 cycles
Rated operational power in W120 W at 240 V DC-13 – electrical durability: 100000 cycles
140 W at 110 V DC-13 – electrical durability: 100000 cycles
140 W at 24 V DC-13 – electrical durability: 100000 cycles
180 W at 60 V DC-13 – electrical durability: 100000 cycles
240 W at 48 V DC-13 – electrical durability: 100000 cycles
15 W at 48 V DC-13 – electrical durability: 1000 cycles
24 W at 24 V DC-13 – electrical durability: 1000 cycles
9 W at 60 V DC-13 – electrical durability: 1000 cycles
Tightening torque1.4 N.m – on screw clamp terminals
height89 mm
Width9.3 mm
Depth66 mm
Net weight0.055 kg
ColourDark grey
Environment
Environmental characteristicNormal environment
product certificationsUKCA
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height1.500 cm
Package 1 Width6.500 cm
Package 1 Length8.700 cm
Package 1 Weight42.000 g
Unit Type of Package 2BB1
Number of Units in Package 210
Package 2 Height9.500 cm
Package 2 Width10.000 cm
Package 2 Length15.000 cm
Package 2 Weight470.000 g
Unit Type of Package 3S02
Number of Units in Package 360
Package 3 Height15.000 cm
Package 3 Width30.000 cm
Package 3 Length40.000 cm
Package 3 Weight3.104 kg
Contractual warranty
Warranty18 months

Main Document

Data Sheet : Download

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “Schneider GVAD1010 | TeSys GV2 & GV3 – auxiliary contact – 1 NO + 1 NO (fault)”

There are no reviews yet.

SHOPPING CART

close
error: Content is protected !!
Let's Chat