Motor power kW | 7.5 kW at 220…230 V AC 50/60 Hz (AC-3) 15 kW at 380…400 V AC 50/60 Hz (AC-3) 15 kW at 415…440 V AC 50/60 Hz (AC-3) 18.5 kW at 500 V AC 50/60 Hz (AC-3) 18.5 kW at 660…690 V AC 50/60 Hz (AC-3) 7.5 kW at 400 V AC 50/60 Hz (AC-4) 7.5 kW at 220…230 V AC 50/60 Hz (AC-3e) 15 kW at 380…400 V AC 50/60 Hz (AC-3e) 15 kW at 415…440 V AC 50/60 Hz (AC-3e) 18.5 kW at 500 V AC 50/60 Hz (AC-3e) 18.5 kW at 660…690 V AC 50/60 Hz (AC-3e) |
---|
Motor power hp | 2 hp at 115 V AC 50/60 Hz for 1 phase motors 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors 10 hp at 200/208 V AC 50/60 Hz for 3 phases motors 10 hp at 230/240 V AC 50/60 Hz for 3 phases motors 20 hp at 460/480 V AC 50/60 Hz for 3 phases motors 25 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
---|
Compatibility code | LC1D |
---|
Pole contact composition | 3 NO |
---|
Protective cover | With |
---|
[Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit 50 A (at 60 °C) for power circuit |
---|
Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 550 A at 440 V for power circuit conforming to IEC 60947 |
---|
Rated breaking capacity | 550 A at 440 V for power circuit conforming to IEC 60947 |
---|
[Icw] rated short-time withstand current | 260 A 40 °C – 10 s for power circuit 430 A 40 °C – 1 s for power circuit 60 A 40 °C – 10 min for power circuit 138 A 40 °C – 1 min for power circuit 100 A – 1 s for signalling circuit 120 A – 500 ms for signalling circuit 140 A – 100 ms for signalling circuit |
---|
Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1 63 A gG at <= 690 V coordination type 1 for power circuit 63 A gG at <= 690 V coordination type 2 for power circuit |
---|
Average impedance | 2 mOhm – Ith 50 A 50 Hz for power circuit |
---|
Power dissipation per pole | 2 W AC-3 5 W AC-1 2 W AC-3e |
---|
[Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified |
---|
Overvoltage category | III |
---|
Pollution degree | 3 |
---|
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
---|
Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
---|
Mechanical durability | 15 Mcycles |
---|
Electrical durability | 1.65 Mcycles 32 A AC-3 at Ue <= 440 V 1.4 Mcycles 50 A AC-1 at Ue <= 440 V 1.65 Mcycles 32 A AC-3e at Ue <= 440 V |
---|
Control circuit type | AC at 50/60 Hz standard |
---|
Coil technology | Without built-in suppressor module |
---|
Control circuit voltage limits | 0.3…0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz 0.8…1.1 Uc (-40…60 °C):operational AC 50 Hz 0.85…1.1 Uc (-40…60 °C):operational AC 60 Hz 1…1.1 Uc (60…70 °C):operational AC 50/60 Hz |
---|
Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C) 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
---|
Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C) 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
---|
Heat dissipation | 2…3 W at 50/60 Hz |
---|
Operating time | 12…22 ms closing 4…19 ms opening |
---|
Maximum operating rate | 3600 cyc/h 60 °C |
---|
Connections – terminals | Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…2.5 mm² – cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: solid without cable end Power circuit: screw clamp terminals 1 2.5…10 mm² – cable stiffness: flexible without cable end Power circuit: screw clamp terminals 2 2.5…10 mm² – cable stiffness: flexible without cable end Power circuit: screw clamp terminals 1 1…10 mm² – cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1.5…6 mm² – cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 1.5…10 mm² – cable stiffness: solid without cable end Power circuit: screw clamp terminals 2 2.5…10 mm² – cable stiffness: solid without cable end |
---|
Tightening torque | Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2 Power circuit: 2.5 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm Power circuit: 2.5 N.m – on screw clamp terminals – with screwdriver Philips No 2 Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver pozidriv No 2 Power circuit: 2.5 N.m – on screw clamp terminals – with screwdriver pozidriv No 2 |
---|
auxiliary contact composition | 1 NO + 1 NC |
---|
Auxiliary contacts type | Type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1 |
---|
Signalling circuit frequency | 25…400 Hz |
---|
Minimum switching voltage | 17 V for signalling circuit |
---|
Minimum switching current | 5 mA for signalling circuit |
---|
Insulation resistance | > 10 MOhm for signalling circuit |
---|
Non-overlap time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
---|
Mounting support | Plate Rail |
---|