-48%

Schneider LC1D40AB7 | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 40 A – 24 V AC 50/60 Hz coil

Schneider Electric
Availability:

Out of stock


Schneider LC1D40AB7 | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 40 A – 24 V AC 50/60Hz coil

4,420.81 EGP 8,501.55 EGP

Out of stock

Schneider LC1D40AB7 | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 40 A – 24 V AC 50/60Hz coil

Technical Specifications

  • Model: LC1D40AB7

  • Series: TeSys D

  • Type: Electromechanical Contactor

  • Number of Poles: 3P (3 Normally Open contacts – 3 NO)

  • Control Circuit Voltage: 24 V AC, 50/60 Hz

  • Main Circuit Voltage: Up to 440 V AC

  • Rated Operational Current (Ie):

    • AC-3 Duty (for motor control): 40 A at 440 V

  • Rated Operational Power (AC-3):

    • 18.5 kW @ 400/415 V (3-phase motor)

  • Auxiliary Contacts: Optional (can be added via clip-on modules)

  • Mounting: DIN rail or screw mounting

  • Conformity: IEC 60947-4-1 and IEC 60947-5-1

  • Electrical Durability: Up to 1.5 million cycles (AC-3 duty)

  • Mechanical Durability: Up to 10 million cycles

  • Operating Temperature: -5°C to +60°C

  • Protection Class: IP20 (with terminal shrouds)

  • Certifications: CE, UL, CSA, EAC

Key Features

  1. Robust 3-Pole Switching Capability:
    The LC1D40AB7 features three normally open (3 NO) main contacts, enabling reliable control of three-phase loads such as motors and resistive loads.

  2. High-Performance AC-3 Rating:
    With a 40 A current rating for AC-3 duty, this contactor is ideal for starting and stopping motors up to 18.5 kW (at 400V), which covers a wide range of industrial machinery and HVAC equipment.

  3. Low Voltage Control Coil (24 V AC):
    The 24 V AC coil is suitable for control circuits where low-voltage operation is needed, improving operational safety and compatibility with control systems.

  4. Compact and Modular Design:
    The TeSys D series is known for its compact footprint and modular architecture, allowing easy integration into electrical panels and straightforward installation alongside other Schneider components.

  5. Flexible Mounting Options:
    Can be mounted on a DIN rail or via screws, providing flexibility for panel designers and installers.

  6. Long Mechanical and Electrical Life:
    Built for endurance, the LC1D40AB7 offers up to 10 million mechanical operations and 1.5 million electrical operations under typical AC-3 loads.

  7. Wide Accessory Range:
    Compatible with a full range of TeSys D accessories such as auxiliary contact blocks, thermal overload relays, timer blocks, and mechanical interlocks, enhancing its versatility in control applications.

  8. Compliance with Global Standards:
    Certified under IEC, UL, CSA, and other international standards, making it suitable for worldwide applications.

Typical Applications

  1. Motor Control:
    Ideal for controlling three-phase motors in conveyors, pumps, compressors, and industrial automation setups. Provides reliable start/stop control and integration into motor starter circuits.

  2. Lighting and HVAC Systems:
    Used in commercial buildings and industrial facilities to switch and control large lighting banks or HVAC equipment with moderate inductive loads.

  3. Heating and Resistive Load Switching:
    Suitable for switching resistive loads such as electric heaters and ovens where precise control and high reliability are essential.

  4. Control Panels and Starters:
    A core component in motor starter panels, including direct-on-line (DOL) starters, reversing starters, and star-delta starters.

  5. Process Automation:
    Used in automated machinery and PLC-controlled systems where it serves as the interface between control signals and power circuits.

SKU: LC1D40AB7 Category: Brand:
Main
Range TeSys
TeSys Deca
Range of product TeSys Deca
product or component type Contactor
Device short name LC1D
contactor application Motor control
Resistive load
Utilisation category AC-4
AC-1
AC-3
AC-3e
Poles description 3P
[Ue] rated operational voltage Power circuit: <= 690 V AC 25…400 Hz
Power circuit: <= 300 V DC
[Ie] rated operational current 60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
40 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
40 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage 24 V AC 50/60 Hz
Complementary
Motor power kW 18.5 kW at 380…400 V AC 50/60 Hz (AC-3)
11 kW at 220…230 V AC 50/60 Hz (AC-3)
22 kW at 415…440 V AC 50/60 Hz (AC-3)
22 kW at 500 V AC 50/60 Hz (AC-3)
30 kW at 660…690 V AC 50/60 Hz (AC-3)
9 kW at 400 V AC 50/60 Hz (AC-4)
18.5 kW at 380…400 V AC 50/60 Hz (AC-3e)
11 kW at 220…230 V AC 50/60 Hz (AC-3e)
22 kW at 415…440 V AC 50/60 Hz (AC-3e)
22 kW at 500 V AC 50/60 Hz (AC-3e)
30 kW at 660…690 V AC 50/60 Hz (AC-3e)
Motor power hp 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
10 hp at 230/240 V AC 50/60 Hz for 3 phases motors
30 hp at 575/600 V AC 50/60 Hz for 3 phases motors
10 hp at 200/208 V AC 50/60 Hz for 3 phases motors
3 hp at 115 V AC 50/60 Hz for 1 phase motors
30 hp at 460/480 V AC 50/60 Hz for 3 phases motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover With
[Ith] conventional free air thermal current 10 A (at 60 °C) for signalling circuit
60 A (at 60 °C) for power circuit
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 800 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 320 A 40 °C – 10 s for power circuit
720 A 40 °C – 1 s for power circuit
72 A 40 °C – 10 min for power circuit
165 A 40 °C – 1 min for power circuit
100 A – 1 s for signalling circuit
120 A – 500 ms for signalling circuit
140 A – 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
80 A gG at <= 690 V coordination type 1 for power circuit
80 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 1.5 mOhm – Ith 60 A 50 Hz for power circuit
Power dissipation per pole 2.4 W AC-3
5.4 W AC-1
2.4 W AC-3e
[Ui] rated insulation voltage Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage category III
Pollution degree 3
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability 6 Mcycles
Electrical durability 1.4 Mcycles 60 A AC-1 at Ue <= 440 V
1.5 Mcycles 40 A AC-3 at Ue <= 440 V
1.5 Mcycles 40 A AC-3e at Ue <= 440 V
Control circuit type AC at 50/60 Hz standard
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3…0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8…1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85…1.1 Uc (-40…60 °C):operational AC 60 Hz
1…1.1 Uc (60…70 °C):operational AC 50/60 Hz
Inrush power in VA 140 VA 60 Hz cos phi 0.75 (at 20 °C)
160 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA 13 VA 60 Hz cos phi 0.3 (at 20 °C)
15 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation 4…5 W at 50/60 Hz
Operating time 4…19 ms opening
12…26 ms closing
Maximum operating rate 3600 cyc/h 60 °C
Connections – terminals Control circuit: screw clamp terminals 2 1…2.5 mm² – cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: solid without cable end
Power circuit: screw connection 1 1…35 mm² – cable stiffness: flexible without cable end
Power circuit: screw connection 2 1…25 mm² – cable stiffness: flexible without cable end
Power circuit: screw connection 1 1…35 mm² – cable stiffness: flexible with cable end
Power circuit: screw connection 2 1…25 mm² – cable stiffness: flexible with cable end
Power circuit: screw connection 1 1…35 mm² – cable stiffness: solid without cable end
Power circuit: screw connection 2 1…25 mm² – cable stiffness: solid without cable end
Tightening torque Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2
Power circuit: 8 N.m – on EverLink BTR screw connectors – cable 25…35 mm² hexagonal screw head 4 mm
Power circuit: 5 N.m – on EverLink BTR screw connectors – cable 1…25 mm² hexagonal screw head 4 mm
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver pozidriv No 2
Power circuit: 2.5 N.m – on screw clamp terminals – with screwdriver pozidriv No 2
auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency 25…400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting support Plate
Rail
Environment
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
IEC 60335-1
Product certifications UL
GOST
CSA
CCC
IP degree of protection IP20 front face conforming to IEC 60529
Protective treatment TH conforming to IEC 60068-2-30
Climatic withstand Conforming to IACS E10 exposure to damp heat
conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device -40…60 °C
60…70 °C with derating
Operating altitude 0…3000 m
Fire resistance 850 °C conforming to IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations contactor open (2 Gn, 5…300 Hz)
Vibrations contactor closed (4 Gn, 5…300 Hz)
Shocks contactor closed (15 Gn for 11 ms)
Shocks contactor open (10 Gn for 11 ms)
Height 122 mm
Width 55 mm
Depth 120 mm
net weight 0.85 kg
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 6.2 cm
Package 1 Width 13.5 cm
Package 1 Length 15.5 cm
Package 1 Weight 917.0 g
Unit Type of Package 2 S02
Number of Units in Package 2 10
Package 2 Height 15.0 cm
Package 2 Width 30.0 cm
Package 2 Length 40.0 cm
Package 2 Weight 9.906 kg
Unit Type of Package 3 P06
Number of Units in Package 3 160
Package 3 Height 77.0 cm
Package 3 Width 80.0 cm
Package 3 Length 60.0 cm
Package 3 Weight 166.98 kg
Contractual warranty
Warranty 18 months

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “Schneider LC1D40AB7 | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 40 A – 24 V AC 50/60 Hz coil”