| utilisation category |
AC-3
AC-3e
AC-1
AC-4 |
| Poles description |
3P |
| power pole contact composition |
3 NO |
| [Ue] rated operational voltage |
Power circuit: <= 690 V AC <= 400 Hz
Signalling circuit: <= 690 V AC <= 400 Hz |
| [Ie] rated operational current |
12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
12 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit |
| Control circuit type |
AC at 50/60 Hz |
| [Uc] control circuit voltage |
220...230 V AC 50/60 Hz |
| Motor power kW |
3 kW at 220...230 V AC 50/60 Hz AC-3
5.5 kW at 380...415 V AC 50/60 Hz AC-3
5.5 kW at 440 V AC 50/60 Hz AC-3
4 kW at 690 V AC 50/60 Hz AC-3
3 kW at 220...230 V AC 50/60 Hz AC-3e
5.5 kW at 380...415 V AC 50/60 Hz AC-3e
5.5 kW at 440 V AC 50/60 Hz AC-3e
4 kW at 690 V AC 50/60 Hz AC-3e
3 kW at 220...230 V AC 50/60 Hz AC-4
5.5 kW at 380...415 V AC 50/60 Hz AC-4
5.5 kW at 440 V AC 50/60 Hz AC-4
4 kW at 690 V AC 50/60 Hz AC-4 |
| Auxiliary contact composition |
1 NC |
| [Uimp] rated impulse withstand voltage |
8 kV |
| Overvoltage category |
III |
| [Ith] conventional free air thermal current |
20 A (at 60 °C) for power circuit
10 A (at 50 °C) for signalling circuit |
| Irms rated making capacity |
144 A AC for power circuit conforming to IEC 60947
110 A AC for signalling circuit conforming to IEC 60947 |
| Rated breaking capacity |
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947 |
| [Icw] rated short-time withstand current |
115 A 50 °C - 1 s for power circuit
105 A 50 °C - 5 s for power circuit
100 A 50 °C - 10 s for power circuit
75 A 50 °C - 30 s for power circuit
55 A 50 °C - 1 min for power circuit
50 A 50 °C - 3 min for power circuit
25 A 50 °C - >= 15 min for power circuit
80 A - 1 s for signalling circuit
90 A - 500 ms for signalling circuit
110 A - 100 ms for signalling circuit |
| Associated fuse rating |
25 A gG at <= 440 V for power circuit
25 A aM for power circuit
10 A gG for signalling circuit conforming to IEC 60947
10 A gG for signalling circuit conforming to VDE 0660 |
| Average impedance |
3 mOhm - Ith 20 A 50 Hz for power circuit |
| Insulation resistance |
> 10 MOhm for signalling circuit |
| Inrush power in VA |
30 VA (at 20 °C) |
| Hold-in power consumption in VA |
4.5 VA (at 20 °C) |
| Heat dissipation |
1.3 W |
| Control circuit voltage limits |
Operational: 0.8...1.15 Uc (at <50 °C) Drop-out: >= 0.20 Uc (at <50 °C) |
| Connections - terminals |
Screw clamp terminals 1 cable(s) 1.5…4 mm²solid
Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1.5…4 mm²solid
Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end |
| Maximum operating rate |
3600 cyc/h |
| Auxiliary contacts type |
Type instantaneous 1 NC |
| Signalling circuit frequency |
<= 400 Hz |
| Minimum switching current |
5 mA for signalling circuit |
| Minimum switching voltage |
17 V for signalling circuit |
| Operating time |
10...20 ms coil de-energisation and NO opening
10...20 ms coil energisation and NO closing |
| Safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Non overlap distance |
0.5 mm |
| Mechanical durability |
10 Mcycles |
| Electrical durability |
1.3 Mcycles 12 A AC-3 at Ue <= 440 V
1.3 Mcycles 12 A AC-3e at Ue <= 440 V
0.3 Mcycles 20 A AC-1 at Ue <= 690 V
0.02 Mcycles 72 A AC-4 at Ue <= 440 V |
| Mechanical robustness |
Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
| height |
58 mm |
| Width |
45 mm |
| Depth |
57 mm |
There are no reviews yet.