-35%
,

Schneider VPL12N | Power Factor controller – VarPlus Logic – VPL 12

Schneider Electric
Availability:

In stock


Schneider VPL12N | Power Factor controller – VarPlus Logic – VPL 12

26,468.52 EGP 40,720.80 EGP

In stock

Schneider VPL12N | Power Factor controller – VarPlus Logic – VPL 12

Product Overview: Schneider VPL12N Power Factor Controller – VarPlus Logic VPL 12

The Schneider Electric VPL12N is a VarPlus Logic VPL 12 power factor controller, engineered to regulate reactive power by automatically controlling capacitor banks. With 12 output steps, it provides precise compensation and optimized energy efficiency in demanding electrical systems.

Key Features:

  • Brand: Schneider Electric

  • Series: VarPlus Logic

  • Model Number: VPL12N

  • Type: Power Factor Controller

  • Model Name: VPL 12

  • Display: Digital LCD with navigation keys

Technical Specifications:

  • Number of Steps: 12 output control steps

  • Power Supply Voltage: Typically 230 V AC (confirm via datasheet)

  • Control Logic: Intelligent step switching algorithm

  • Display Language: Multi-language interface

  • Mounting Type: Panel-mounted

  • Communication: RS-485 Modbus (on selected versions)

  • Ambient Temperature Range: Suitable for industrial environments

  • Protection Features: Harmonic distortion detection, voltage limits, and alarm settings

Functional Features:

  • Automatic Step Switching:
    – Adjusts capacitor steps based on real-time reactive power measurement

  • Alarm Management:
    – Detects anomalies like over-voltage or over-compensation

  • Auto/Manual Control:
    – Operator flexibility for various system needs

  • Self-Diagnostics:
    – Built-in system health checks for reliability

  • Data Logging:
    – Operational records for easy maintenance and troubleshooting

Applications:

  • Large-scale industrial power factor correction panels

  • Commercial facilities with dynamic reactive loads

  • Energy-saving projects

  • Heavy machinery operations

  • Power distribution systems requiring precision compensation

Benefits:

  • Enhanced Energy Efficiency:
    – Minimizes reactive power consumption and improves system power factor

  • Cost Reduction:
    – Helps avoid utility penalties due to poor power factor

  • User-Friendly Interface:
    – Simple setup and real-time monitoring

  • Flexible Integration:
    – Easily connects with new or existing capacitor banks

  • High Performance:
    – Stable operation under various load and voltage conditions

Typical Industries:

  • Manufacturing and processing plants

  • HVAC systems

  • Hospitals and data centers

  • Mining and metals

  • Commercial and institutional buildings

SKU: VPL12N Categories: , Brand:
Main
Range PowerLogic
Product name PowerLogic PFC Controller
Device short name VPL12
Product or component typee Power factor controller
Complementary
Number of step output contacts 12
[Us] rated supply voltage 90…550 V AC
<= 999 kV AC with external VT
Measurement current 0…5 A
Measurement voltage 90…550 V AC 50/60 Hz
Operating mode Manual or automatic
Number of quadrant operation for generator application 4
Device connection Communication protocol: Modbus interface: RS485
Input function Switch: 1 x dry contact
Colour code Front: dark grey RAL 7016
Display type Backlit LCD
Display size 56 x 25 mm
Function available Manual programming
Automatic initialisation
Automatic detection
Advanced programming (expert)
Any step sequence
Metering type Power factor and displacement PF (signed, four quadrant)
Total current harmonic distortion THD (I)
Power factor average over lifetime
Temperature maximum
Phase current I1, I2, I3 RMS on load
Active power P, P1, P2, P3 on load
Reactive power Q, Q1, Q2, Q3 on load
Apparent power S, S1, S2, S3 on load
Voltage U21, U32, U13, V1, V2, V3 on load
Type of measurement Capacitor current overload Irms/I1
Individual voltage harmonic
Power factor
Operating time
Cos φ
Ambient temperature inside the cubicle
Tan φ
Information displayed Number of switching cycles per step
Individual step size in kVAr
Remaining step capacity in %
Type of alarms Step power loss (< 75 %) / Action: message and alarm contact + step blocked Step faulty / Action: message and alarm contact + step blocked High current (> 6 A CT) / Action: message and alarm contact
Hunting (unstable regulation) / Action: message and alarm contact + step blocked
Low current (< 15 mA CT) / Action: message and alarm contact Overcompensation / Action: message and alarm contact Capacitor current overload (Irms/I1) (> 130 % I1) / Action: message and alarm contact + step switched off
Overtemperature (50 °C) / Action: message and alarm contact + step switched off
Overtemperature (30 °C) / Action: fan switch
Overvoltage (+/- 10 %) / Action: message and alarm contact + control stopped
Total harmonic distortion (> 7 %) / Action: message and alarm contact + step switched off
data recording 5 alarms
Operational Hours alarm 100000 h without maintenance
Operational counter alarm 65000 cycles without maintenance
input type Phase to phase
Phase to neutral
Insensitive to CT polarity
Insensitive to phase rotation polarity
Current input CT…X/5 A and X/1 A
Output type Control relay: 0.2 A 110 V DC
Control relay: 1 A 48 V DC
Control relay: 2 A 400 V AC 50/60 Hz
Control relay: 1 A 24 V DC
Control relay: 5 A 250 V AC 50/60 Hz
Control relay: 5 A 120 V AC 50/60 Hz
Fan: 5 A 250 V AC 50/60 Hz
Fan: 1 A 48 V DC
Alarm relay: 5 A 250 V AC 50/60 Hz
Alarm relay: 1 A 48 V DC
Maximum at the common terminal 10 A
Settings operating mode Automatic
Manual
Type of setting Choice of stepping programs: auto
Choice of stepping programs: LIFO
Choice of stepping programs: linear
Delay between 2 successive switch on the same step: 5…1200 s
Step configuration programming: auto
Step configuration programming: off
Step configuration programming: fixed
Target cos phi: 0.7 inductive…0.7 capacitive
Target cos phi: dual cos φ
Measurement accuracy Voltage +/- 1 %
Current +/- 1 %
Frequency +/- 1 %
Energy (P,Q,S) +/- 2 %
Cos φ +/- 2 %
Total voltage harmonic distortion THD (U) +/- 2 %
Individual voltage harmonic +/- 3 %
Temperature +/- 3 °C
Time delay range 1…6500 s (on reconnection)
1…6500 s (on response)
Provided equipment User manual
Mounting mode Flush-mounted
Mounting support Panel – thickness: 1…3 mm
Mounting location In cabinet
Cut-out dimensions 138 x 138 mm
height 144 mm
Width 144 mm
Depth 58 mm
Net weight 0.6 kg
Environment
Standards IEC 61000-6-4
UL 61010-1
EN 61010-1
IEC 61000-6-2
IEC 61326-1
product certifications EAC
NRTL
cNRTL
CE
IP degree of protection Front face: IP41
Rear face: IP20
Operating altitude <= 2000 m
ambient air temperature for operation -20…60 °C
Ambient air temperature for storage -40…85 °C
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 9.200 cm
Package 1 Width 17.700 cm
Package 1 Length 18.400 cm
Package 1 Weight 724.000 g
Unit Type of Package 2 S03
Number of Units in Package 2 8
Package 2 Height 30.000 cm
Package 2 Width 30.000 cm
Package 2 Length 40.000 cm
Package 2 Weight 6.155 kg
Unit Type of Package 3 P06
Number of Units in Package 3 64
Package 3 Height 75.000 cm
Package 3 Width 60.000 cm
Package 3 Length 80.000 cm
Package 3 Weight 58.408 kg

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “Schneider VPL12N | Power Factor controller – VarPlus Logic – VPL 12”

There are no reviews yet.

SHOPPING CART

close
Let's Chat