CAD overall width | 29 mm |
---|
CAD overall height | 29 mm |
---|
CAD overall depth | 83 mm |
---|
Terminals description ISO n°1 | (23-24)NO (13-14)NO |
---|
Device mounting | Fixing hole – diameter: 22.5 mm 22.3 +0.4/0 conforming to IEC 60947-1 |
---|
Fixing center | >= 30 x 40 mm (support panel) metal – thickness: 1…6 mm >= 30 x 40 mm (support panel) plastic – thickness: 2…6 mm |
---|
Fixing mode | Fixing nut: 2…2.4 N.m |
---|
Contact operation | Slow-break |
---|
Mechanical durability | 300000 cycles |
---|
Connections – terminals | Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to IEC 60947-1 Screw clamp terminals, 1 x 0.34…2 x 2.5 mm² without cable end conforming to IEC 60947-1 |
---|
Tightening torque | 0.8…1.2 N.m conforming to IEC 60947-1 |
---|
Shape of screw head | Cross compatible with JIS No 1 screwdriver Cross compatible with Philips no 1 screwdriver Cross compatible with pozidriv No 1 screwdriver Slotted compatible with flat Ø 4 mm screwdriver Slotted compatible with flat Ø 5.5 mm screwdriver |
---|
Short-circuit protection | 4 A cartridge fuse type gG conforming to IEC 60947-5-1 |
---|
[Ui] rated insulation voltage | 250 V (pollution degree 3) conforming to IEC 60947-1 |
---|
[Uimp] rated impulse withstand voltage | 4 kV conforming to IEC 60947-1 |
---|
[Ie] rated operational current | 0.1 A at 250 V, DC-13, R300 conforming to IEC 60947-5-1 0.22 A at 125 V, DC-13, R300 conforming to IEC 60947-5-1 0.3 A at 240 V, AC-14, D300 conforming to IEC 60947-5-1 0.6 A at 120 V, AC-14, D300 conforming to IEC 60947-5-1 |
---|
Electrical durability | 1000000 cycles, DC-13, 0.3 A at 24 V, operating rate <216000 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C 1000000 cycles, AC-15, 0.03 A at 230 V, operating rate <216000 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C 1000000 cycles, AC-15, 0.09 A at 240 V, operating rate <108000 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C |
---|
Electrical reliability | Λ < 10exp(-6) at 17 V and 5 mA conforming to IEC 60947-5-4 |
---|